Schneider Electric ComPacT NSX Mode d'emploi

PDF
Document
Schneider Electric ComPacT NSX Mode d'emploi | Fixfr
/

User questions

F V

Jennifer F.

What should be checked if a ComPacT NSX circuit breaker cannot be engaged after charging?

Verify if the breaker is already closed, ensure the actuator is not in manual mode, and check that the locking switch on the IFM or IFE interface is open. If the breaker has tripped, it must be reset before it can be closed again.

F V

Jennifer F.

Why is the circuit breaker unable to close after being charged?

If the circuit breaker will not close, verify whether it is already in the closed position, ensure the actuator is not in manual mode, and check if the locking switch on the interface is in the closed position. Additionally, if the breaker has tripped, it must be reset before it can accept new commands.

F V

Jennifer F.

What to do if the circuit breaker cannot be engaged after charging?

Check if the breaker is already closed, ensure it is not in manual mode, and verify that the locking switch is not active. If the device has tripped, it must be reset before it can accept new commands.

F V

Jennifer F.

What should be checked if the ComPacT NSX circuit breaker cannot be switched on after charging?

Check if the breaker is already closed (error 152 in the status register), verify that the actuator is not in manual mode (error 155), and ensure the interlock switch on the IFM/IFE interface is not in the closed position (error 2). If the device has tripped, it must be reset (error 151) before it can accept commands. Specific error codes can be identified in the command status register (8021).

F V

Jennifer F.

How to troubleshoot a ComPacT NSX breaker that will not close after being charged?

Check if the breaker is already closed (error 152), ensure the actuator is not in manual mode (error 155), verify that the IFM/IFE locking switch is not in the closed position (error 2), and confirm if the device needs a reset after a trip (error 151).

F V

Jennifer F.

Why might a ComPacT NSX circuit breaker fail to engage after charging?

Possible causes include the breaker already being in the closed position, the actuator being set to manual mode, the locking switch being active, or the device being in a tripped state which requires a reset before it can be closed.

Preparing document for printing…