Linda V.

What are the requirements for the initial start-up of the device?

The main power supply must be turned on at least 6 hours before operating the product to protect the compressor. Transmission lines and power supply wiring should be separated to avoid electronic noise. Additionally, the water pump speed should not be set to the minimum level to ensure proper flow.

V E

Linda V.

How should the hydraulic system be prepared and filled during commissioning?

Check all water inlet and outlet connections and ensure stop valves are assembled correctly. The water supply pressure should be approximately 3.0 bar. When filling the system, increase pressure from 0 to 2.0 bar gradually over at least 1 minute and perform air purging at the highest point of the system.