Robert S.
How to resolve a smoke temperature fault exceeding 100 °C?
Inspect the insulated hoses to ensure normal water circulation in the condenser. Clean the heating body and the condenser. Verify that the turbulators are present and in good condition within the smoke tubes. Check the condition of the burner. The safety thermostat can be manually reset after removing its cap.